LC100 Loop Calibrator

Seite 2 - Table of Contents

A. Milliamp SourceFigure 3 shows a typical application where theLC100 is sourcing 4 to 20 mA into a deviceunder test.Figure 3 - Sourcing 4 to 20 mA1)

Seite 3

95) The auto step feature provides automatedoutput changes. Refer to the Auto ModesSection of the manual for more information.B. Milliamp SimulationF

Seite 4

D. Milliamp Measure with Loop PowerAgain, Figure 5 shows the proper connections.But in this case the device under test is a two-wire transmitter that

Seite 5

input impedance of the LC100 ≥ 1 meg ohmwhile in this mode.Figure 6 - Measuring 0 to 28 VDC5. Advanced Operating ModesA. Auto Step/Ramp ModeThe LC100

Seite 6

3) Press the key once for the stepmode, twice for the slow ramp mode andthree times for the fast ramp mode. Witheach press a small annunciator will

Seite 7 - 2. Nomenclature

6) When the key is released the %display will return to normal operation.C. Min/Max DataloggingWhen the LC100 is in any of the measuremodes (mA, mA

Seite 8 - 3. Getting Started

6. MaintenanceA. Battery SelectionThe LC100 operates on a standard 9V alkalinebattery or an optional rechargeable 9V Ni-Cdbattery. For most applicati

Seite 9 - 4. Basic Operating Modes

1-800-821-0023 or www.martelcorp.com.7. SpecificationsInput Range: 0.000 to 24.000–25.00% to 125.00%Output Range 0.000 to 24.000Source/Simulate: –25.0

Seite 10 - A. Milliamp Source

8. WarrantyMartel Electronics Corporation warrants all prod-ucts against material defects and workmanship fora period of twelve (12) months after the

Seite 12 - E. Voltage Measure

Table of Contents1. Introduction1.1 Customer Service . . . . . . . . . . . . . . . .11.2 Unpacking . . . . . . . . . . . . . . . . . . . . .21.3 Saf

Seite 13 - 5. Advanced Operating Modes

0219053 5/08 Rev Ewww.martelcorp.come-mail: [email protected]: (603) 434-8179 800-821-0023 Fax: (603) 434-1653 Martel Electronics3 Cor

Seite 14 - B. Percent Error Mode

1LC100 1. IntroductionThe Martel LC100 is designed to be a complete4 to 20mA current calibrator for both trouble-shooting and calibrating current loop

Seite 15 - C. Min/Max Datalogging

21.2 UnpackingRemove the packing list and verify that allequipment has been received. If there are anyquestions about the shipment please call Martel

Seite 16 - 6. Maintenance

3Double InsulatedElectric ShockFusePE GroundHot Surface (Burn Hazard)Read the User’s Manual (Important Information)OffOnCanadian Standards Association

Seite 17 - 7. Specifications

4WarningTo avoid possible electric shock or personal injury:• Do not apply more than the rated voltage.See specifications for supported ranges. • Foll

Seite 18 - 8. Warranty

5CautionTo avoid possible damage to calibrator orto equipment under test:• Use the proper jacks, function, and range foryour measurement or sourcing a

Seite 19

63. Getting StartedA. Battery Save FeatureAfter unpacking the LC100, it should be readyfor use. A 9 volt alkaline battery comes pre-installed. The “B

Seite 20 - 0219053 5/08 Rev E

Communicator during calibration or installationof HART™ transmitters. The internal resistortakes the place of the 250 ohm resistor normal-ly installe